Connecting the StorEdge Interface to AC

Connecting the StorEdge Interface to AC
NOTE
The AC is used for auxiliary power only and does not carry high power.
Use a three-wire cable with a cross section of 1-2mm
To connect to AC:
 1.  Turn OFF the AC power source to be connected to the interface.
 2.  Remove the interface AC sealing gland.
 3.  Strip off 5/16" (8mm) of the AC cable insulation and expose two line wires and one grounding wire.
 4.  Insert the wire ends into the AC  terminals (L, N), and the grounding terminal according to the labels. 

Connecting the StorEdge Interface to the Battery Pack

WARNING!
The battery should be powered OFF before and during wiring. Turn OFF:
The auxiliary power supply switch
l
The circuit breaker switch
l
Before installing the battery pack according to the instructions   p rovided by the battery manufacturer, 
connect the battery to the StorEdge Interface as described in this section.
 
14
2
Figure 15: AC and grounding connections