GE F60 Instruction Manual page 489

Ur series
Hide thumbs Also See for F60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 35 of 55)
ADDR
REGISTER NAME
955C
...Repeated for Direct Input/Output 30
9568
...Repeated for Direct Input/Output 31
9574
...Repeated for Direct Input/Output 32
IEC 61850 received integers (read/write setting registers)
9910
IEC61850 GOOSE UInteger 1 default value
9912
IEC61850 GOOSE UInteger input 1 mode
9913
...Repeated for IEC61850 GOOSE UInteger 2
9916
...Repeated for IEC61850 GOOSE UInteger 3
9919
...Repeated for IEC61850 GOOSE UInteger 4
991C
...Repeated for IEC61850 GOOSE UInteger 5
991F
...Repeated for IEC61850 GOOSE UInteger 6
9922
...Repeated for IEC61850 GOOSE UInteger 7
9925
...Repeated for IEC61850 GOOSE UInteger 8
9928
...Repeated for IEC61850 GOOSE UInteger 9
992B
...Repeated for IEC61850 GOOSE UInteger 10
992E
...Repeated for IEC61850 GOOSE UInteger 11
9931
...Repeated for IEC61850 GOOSE UInteger 12
9934
...Repeated for IEC61850 GOOSE UInteger 13
9937
...Repeated for IEC61850 GOOSE UInteger 14
993A
...Repeated for IEC61850 GOOSE UInteger 15
993D
...Repeated for IEC61850 GOOSE UInteger 16
FlexElement Actuals (Read Only) (16 modules)
9A01
FlexElement™ 1 Actual
9A03
FlexElement™ 2 Actual
9A05
FlexElement™ 3 Actual
9A07
FlexElement™ 4 Actual
9A09
FlexElement™ 5 Actual
9A0B
FlexElement™ 6 Actual
9A0D
FlexElement™ 7 Actual
9A0F
FlexElement™ 8 Actual
Teleprotection Inputs/Outputs (Read/Write Settings)
9B00
Teleprotection Function
9B01
Teleprotection Number of Terminals
9B02
Teleprotection Number of Channels
9B03
Teleprotection Local Relay ID
9B04
Teleprotection Terminal 1 ID
9B05
Teleprotection Terminal 2 ID
9B06
Reserved (10 items)
9B10
Teleprotection Input 1-n Default States (16 items)
9B30
Teleprotection Input 2-n Default States (16 items)
9B50
Teleprotection Output 1-n Operand (16 items)
9B70
Teleprotection Output 2-n Operand (16 items)
Teleprotection Inputs/Outputs Commands (Read/Write Command)
9B90
Teleprotection Clear Lost Packets
Teleprotection Channel Tests (Read Only)
9B91
Teleprotection Channel 1 Status
9B92
Teleprotection Channel 1 Number of Lost Packets
9B93
Teleprotection Channel 2 Status
9B94
Teleprotection Channel 2 Number of Lost Packets
9B95
Teleprotection Network Status
9BA0
Teleprotection Channel 1 Input States
9BA1
Teleprotection Channel 2 Input States
9BB0
Teleprotection Input 1 States, 1 per register (16 items)
9BC0
Teleprotection Input 2 States, 1 per register (16 items)
GE Multilin
RANGE
0 to 429496295
0 to 1
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
-2147483.647 to 2147483.647
0 to 1
2 to 3
1 to 2
0 to 255
0 to 255
0 to 255
0 to 1
0 to 3
0 to 3
0 to 65535
0 to 65535
0 to 1
0 to 2
0 to 65535
0 to 2
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 1
F60 Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F003
---
1
F491
0 (Default Value)
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
0.001
F004
---
1
F102
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
---
F001
---
1
F086
---
1
F086
---
1
F300
---
1
F300
---
1
F126
---
1
F134
---
1
F001
---
1
F134
---
1
F001
---
1
F134
---
1
F500
---
1
F500
---
1
F108
---
1
F108
DEFAULT
1000
B
0
0
0
0
0
0
0
0
0 (Disabled)
2
1
0
0
0
0
0 (Off)
0 (Off)
0
0
0 (No)
1 (OK)
0
1 (OK)
0
2 (n/a)
0
0
0 (Off)
0 (Off)
B-43

Advertisement

Table of Contents
loading