5.2 PRODUCT SETUP
An example user display setup and result is shown below:
USER DISPLAY 1
USER DISPLAYS
5
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
DIRECT I/O
Direct inputs and outputs are intended for exchange of status information (inputs and outputs) between UR-series relays
connected directly via type 7 digital communications cards. The mechanism is very similar to IEC 61850 GSSE, except that
communications takes place over a non-switchable isolated network and is optimized for speed. On type 7 cards that sup-
port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output
5-60
DISP 1 TOP LINE:
Current X
DISP 1 BOTTOM LINE:
MESSAGE
Current Y
DISP 1 ITEM 1:
MESSAGE
6016
DISP 1 ITEM 2:
MESSAGE
6357
DISP 1 ITEM 3:
MESSAGE
0
DISP 1 ITEM 4:
MESSAGE
0
DISP 1 ITEM 5:
MESSAGE
0
Current X
Current Y
DIRECT I/O
DIRECT OUTPUT
DEVICE ID: 1
DIRECT I/O CH1 RING
MESSAGE
CONFIGURATION: Yes
DIRECT I/O CH2 RING
MESSAGE
CONFIGURATION: Yes
DIRECT I/O DATA
MESSAGE
RATE: 64 kbps
DIRECT I/O CHANNEL
MESSAGE
CROSSOVER: Disabled
CRC ALARM CH1
MESSAGE
CRC ALARM CH2
MESSAGE
UNRETURNED
MESSAGE
MESSAGES ALARM CH1
UNRETURNED
MESSAGE
MESSAGES ALARM CH2
F60 Feeder Protection System
Shows user-defined text with first Tilde marker.
~
A
Shows user-defined text with second Tilde marker.
~
A
Shows decimal form of user-selected Modbus Register
Address, corresponding to first Tilde marker.
Shows decimal form of user-selected Modbus
Register Address, corresponding to 2nd Tilde marker.
This item is not being used - there is no corresponding
Tilde marker in Top or Bottom lines.
This item is not being used - there is no corresponding
Tilde marker in Top or Bottom lines.
This item is not being used - there is no corresponding
Tilde marker in Top or Bottom lines.
Shows the resultant display content.
0.850 A
0.327 A
Range: 1 to 16
Range: Yes, No
Range: Yes, No
Range: 64 kbps, 128 kbps
Range: Disabled, Enabled
See page 5–66.
See page 5–66.
See page 5–67.
See page 5–67.
5 Z SETTINGS
5.2.17 DIRECT INPUTS/OUTPUTS
GE Multilin