GE F60 Instruction Manual page 482

Ur series
Hide thumbs Also See for F60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 28 of 55)
ADDR
REGISTER NAME
754F
Disconnect switch 1 operate time
7550
Disconnect switch 1 alarm delay
7552
Disconnect switch 1 events
7553
Reserved (2 items)
7555
...Repeated for disconnect switch 2
B
756A
...Repeated for disconnect switch 3
757F
...Repeated for disconnect switch 4
7594
...Repeated for disconnect switch 5
75A9
...Repeated for disconnect switch 6
75BE
...Repeated for disconnect switch 7
75D3
...Repeated for disconnect switch 8
High Impedance Fault Detection (Hi-Z) Settings (Read/Write Setting)
7A00
Hi-Z Function
7A01
Hi-Z Signal Source
7A03
Hi-Z Arcing Sensitivity
7A04
Hi-Z Phase Event Count
7A05
Hi-Z Ground Event Count
7A06
Hi-Z Event Count Time
7A07
Hi-Z Overcurrent Protection Coordination Timeout
7A08
Hi-Z Phase Overcurrent Minimum Pickup
7A09
Hi-Z Neutral Overcurrent Minimum Pickup
7A0A
Hi-Z Phase Rate of Change
7A0B
Hi-Z Neutral Rate of Change
7A0C
Hi-Z Loss of Load Threshold
7A0D
Hi-Z 3-Phase Event Threshold
7A0E
Hi-Z Voltage Supervision Threshold
7A0F
Hi-Z Voltage Supervision Delay
7A10
HIZ Even Harmonic Restraint
7A11
Hi-Z Target
7A12
Hi-Z Events
7A12
Hi-Z Arcing Reset Time
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
7B61
User Programmable Pushbutton 1 Top Line
7B6B
User Programmable Pushbutton 1 On Text
7B75
User Programmable Pushbutton 1 Off Text
7B7F
User Programmable Pushbutton 1 Drop-Out Time
7B80
User Programmable Pushbutton 1 Target
7B81
User Programmable Pushbutton 1 Events
7B82
User Programmable Pushbutton 1 LED Operand
7B83
User Programmable Pushbutton 1 Autoreset Delay
7B84
User Programmable Pushbutton 1 Autoreset Function
7B85
User Programmable Pushbutton 1 Local Lock
7B86
User Programmable Pushbutton 1 Message Priority
7B87
User Programmable Pushbutton 1 Remote Lock
7B88
User Programmable Pushbutton 1 Reset
7B89
User Programmable Pushbutton 1 Set
7B8A
User Programmable Pushbutton 1 Hold
7B8B
...Repeated for User Programmable Pushbutton 2
7BB6
...Repeated for User Programmable Pushbutton 3
7BE1
...Repeated for User Programmable Pushbutton 4
7C0C
...Repeated for User Programmable Pushbutton 5
7C37
...Repeated for User Programmable Pushbutton 6
7C62
...Repeated for User Programmable Pushbutton 7
B-36
RANGE
0 to 2
0 to 1000000
0 to 1
---
0 to 1
0 to 5
1 to 10
10 to 250
10 to 500
5 to 180
10 to 200
0.01 to 10
0.01 to 10
1 to 999
1 to 999
5 to 100
1 to 1000
0 to 100
0 to 3000
0 to 100
0 to 2
0 to 1
0 to 6000
0 to 2
---
---
---
0 to 60
0 to 2
0 to 1
0 to 65535
0 to 600
0 to 1
0 to 65535
0 to 2
0 to 65535
0 to 65535
0 to 65535
0 to 10
F60 Feeder Protection System
UNITS
STEP
FORMAT
s
0.001
F001
s
0.001
F003
---
1
F102
---
---
---
---
1
F102
---
1
F167
---
1
F001
---
1
F001
---
1
F001
min
1
F001
s
1
F001
pu
0.01
F001
pu
0.01
F001
A/2cycle
1
F001
A/2cycle
1
F001
%
1
F001
A
1
F001
%
1
F001
cycles
2
F001
%
1
F001
---
1
F109
---
1
F102
s
0.1
F001
---
1
F109
---
---
F202
---
---
F202
---
---
F202
s
0.05
F001
---
1
F109
---
1
F102
---
1
F300
s
0.05
F001
---
1
F102
---
1
F300
---
1
F220
---
1
F300
---
1
F300
---
1
F300
s
0.1
F001
APPENDIX B
DEFAULT
70
0
0 (Disabled)
---
0 (Disabled)
0 (SRC 1)
5
30
30
15
15
150
100
150
150
15
25
5
60
20
0 (Self-reset)
0 (Disabled)
0
2 (Disabled)
(none)
(none)
(none)
0
0 (Self-reset)
0 (Disabled)
0
0
0 (Disabled)
0
0 (Disabled)
0
0
0
1
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents