GE F60 Instruction Manual page 180

Ur series
Hide thumbs Also See for F60:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. Next,
release the pushbutton to automatically start stage 2. Once stage 2 has started, the pushbutton can be released. When
stage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton.
c) TRIP AND ALARM LEDS
PATH: SETTINGS
PRODUCT SETUP
TRIP & ALARM LEDS
The trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Each
indicator can be programmed to become illuminated when the selected FlexLogic™ operand is in the logic 1 state.
d) USER-PROGRAMMABLE LED 1(48)
PATH: SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE
LED 1
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
5
nate when the selected FlexLogic™ operand is in the logic 1 state.
For the standard faceplate, the LEDs are located as follows.
LED Panel 2: user-programmable LEDs 1 through 24
LED Panel 3: user programmable LEDs 25 through 48
For the enhanced faceplate, the LEDs are located as follows.
LED column 2: user-programmable LEDs 1 through 12
LED column 3: user-programmable LEDs 13 through 24
LED column 4: user-programmable LEDs 25 through 36
LED column 5: user-programmable LEDs 37 through 48
Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs.
The user-programmable LED settings select the FlexLogic™ operands that control the LEDs. If the
"Self-Reset" (the default setting), the LED illumination will track the state of the selected LED operand. If the
ting is "Latched", the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com-
munications channel, or from any programmed operand, even if the LED operand state de-asserts.
5-48
USER-PROGRAMMABLE LEDS
TRIP LED INPUT:
Off
ALARM LED INPUT:
MESSAGE
Off
USER-PROGRAMMABLE LEDS
LED 1 OPERAND:
Off
LED 1 TYPE:
MESSAGE
Self-Reset
F60 Feeder Protection System
TRIP & ALARM LEDS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
USER-PROGRAMMABLE LED 1(48)
Range: FlexLogic™ operand
Range: Self-Reset, Latched
LED 1 TYPE
5 Z SETTINGS
setting is
set-
LED 1 TYPE
GE Multilin