d. If L_TYPE is "Direct", the AI Block may be placed in AUTO mode to return the
device to service. Guided Setup does this automatically.
5. If L_TYPE is "Indirect" or "Indirect Square Root", set "OUT_SCALE" to change
engineering units.
a. Select the OUT_SCALE UNITS from the drop down menu.
b. Set the OUT_SCALE low value. This may be elevated or suppressed for level
applications.
c. Set the OUT_SCALE high value. This may be elevated or suppressed for level
applications.
d. If L_TYPE is "Indirect", the AI Block may be placed in AUTO mode to return
the device to service. Guided Setup does this automatically.
6. If L_TYPE is "Indirect Square Root", a "LOW FLOW CUTOFF" function is
available.
a. Enable LOW FLOW CUTOFF.
b. Set the LOW_CUT VALUE in XD_SCALE UNITS.
c. The AI Block may be placed in AUTO mode to return the device to service.
Guided Setup does this automatically.
7. Change damping.
a. To use guided setup:
Navigate to Configure, Guided Setup, and select "Change Damping".
Note
Guided Setup will automatically go through each step in the proper order.
Enter the desired damping value in seconds. The permitted range of
values is 0.4 to 60 seconds.
b. To use manual setup:
Navigate to Configure, Manual Setup, Process Variable, and select
"Change Damping".
Enter the desired damping value in seconds. The permitted range of
values is 0.4 to 60 seconds.
8. Configure LCD display (if installed).
a. To use guided setup:
Navigate to Configure, Guided Setup, and select "Local Display Setup".
Note
Guided setup will automatically go through each step in the proper order.
Check the box next to each parameter to be displayed to a maximum of
four parameters. The LCD display will continuously scroll through the
selected parameters.
b. To use manual setup:
Navigate to Configure, Manual Setup, and select "Local Display Setup".
Check each parameter to be displayed. The LCD display will continuously
scroll through the selected parameters.
9. Review transmitter configuration and place in service.
a. To review the transmitter configuration navigate using the guided setup
navigation sequences for "AI Block Unit Setup", "Change Damping", and
"Set up LCD Display".
Quick Start Guide