Module Base Maintenance; Tools Required; Removing The Module Base - Emerson Fisher FIELDVUE DVC6000 HW2 Instruction Manual

Digital valve controller
Table of Contents

Advertisement

Maintenance and Troubleshooting
June 2017
CAUTION
When replacing components, use only components specified by the factory. Always use proper component replacement
techniques, as presented in this manual. Improper techniques or component selection may invalidate the approvals and
the product specifications, as indicated in table 1‐2. It may also impair operations and the intended function of the device.
Note
If the feedback arm (key 79) or feedback arm assembly (key 84) is removed from the digital valve controller, the travel sensor must
be recalibrated.
Because of the diagnostic capability of the DVC6000 HW2, predictive maintenance is available through the use of
ValveLink software. Using the digital valve controller, valve and instrument maintenance can be enhanced, thus
avoiding unnecessary maintenance. For information on using the ValveLink software, refer to the ValveLink software
online help.

Module Base Maintenance

The digital valve controller contains a module base consisting of the I/P converter, printed wiring board assembly, and
pneumatic relay. The module base may be easily replaced in the field without disconnecting field wiring or tubing.

Tools Required

Table 6‐1 lists the tools required for maintaining the DVC6000 HW2 digital valve controller.
Table 6‐1. Tools Required
Tool
Phillips Screwdriver
Hex key
Hex key
Hex key
Hex key
Hex key
Open‐end wrench
Hex key
Open‐end wrench
Hex key

Removing the Module Base

To remove the DVC6005 HW2 module base, perform the following steps. Refer to figure 7‐2 for key number locations.
WARNING
To avoid personal injury or equipment damage from bursting of parts, turn off the supply pressure to the digital valve
controller and bleed off any excess supply pressure before attempting to remove the module base assembly from the
housing.
64
Size
Relay, printed wiring board assembly, and cover screws
5 mm
Terminal box screw
1.5 mm
Terminal box cover screw
2.5 mm
I/P converter screws
5 mm
Travel sensor screws
6 mm
Module base screws
1/2‐inch
Connector Arm screw (DVC6015)
9/64‐inch
Feedback arm screw
7/16‐inch
DVC6015 mounting bolts
3/16‐inch
DVC6025 mounting bolts
Component
Instruction Manual
D103785X012