Standards And Regulations - Wolf BML Operating Instructions Manual

Table of Contents

Advertisement

Standards / Directives
Installation /
Commissioning
Warnings
3063527_201308
Standards / Regulations
The appliance and control unit accessories comply with the
following regulations:
EC Directives
- 2006/95/EC
Low Voltage Directive
- 2004/108/EC EMC Directive
EN Standards
- EN 60730-1 Automatic electrical controls for household and
similar use
- EN 60730-2-11 Particular requirements for temperature
sensing controls
- EN 61000-6-2 EMC Immunity for industrial environments
- EN 61000-6-3 EMC Emission standard for residential
environments
- According to DIN EN 50110-1, only qualified electricians may
carry out the installation and commissioning of the ventilation
control unit and connected accessories.
- Observe all regulations stipulated by your local power supply
utility and all VDE or local regulations.
- DIN VDE 0100 regulations regarding the installation of high
voltage systems up to 1000 V
- DIN VDE 0105-100 Operation of electrical plants
- Use exclusively original Wolf accessories (electric heater coil,
condensate pump, servomotors, etc.), otherwise the Wolf
warranty will be void.
Only use cables that meet local wiring regulations with regard to
voltage, current, insulation material, load etc. Always fit an earth
conductor.
Power supply:
An externally accessible, omnipolar isolator must be installed
with the appliance. Power cable, external: 3 x 2.5 mm².
Fuse/MCB protection: 230 V/16 A.
RCD
Only AC/DC-sensitive RCDs of type B with 300 mA rating are
permissible.
Connect the power cable and accessories in accordance with
the wiring diagram provided.
A high leakage current can be expected due to the EC
motors. Ensure that a secure earth connection is in place
before connecting the power supply and commencing
commissioning.
For Austria, the ÖVE regulations and local building regulations
apply.
- Removing, bypassing or disabling of safety and monitoring
equipment is not permissible.
- The system must only be operated if it is in perfect technical
condition. Immediately have any faults and damage that may
impact on safety removed.
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cgl

Table of Contents