Control level 3 - Specialist - System parameters

Setting parameters

Specialist
Back
Zone designat
LM001
K20
LM015
25 %
LM016
70 %
LM017
10 K
LM018
93
LM023
ON

Specialist parameter list - Overview

Parameter
LM001
Configuration
LM013
Hysteresis OFF
LM015
Minimum fan speed
LM016
Maximum fan speed
LM017
P component for speed control
LM018
Ratio of extract air to supply air
fan speed
LM020
Weather-compensated
winter/summer changeover
LM021
Differential for heating
LM023
Room frost protection
LM024
Room frost protection
temperature
LM060
Fan speed for Economy
operation, speed control pre-
selection for backup mode, night
ventilation, summer mode, room
frost protection
LM080
P component for heating circuit
mixer
LM081
Integral action time for heating
circuit mixer
26
With the r.h. rotary selector, select the required zone (from
zone 1 to 7) in the "Specialist" menu level (after entering a
password) and press selector to confirm.
Select the ventilation unit parameter (LM...) you want to
modify, confirm by pressing the selector and then modify
it by turning the r.h. rotary selector. Once you have set the
ventilation unit parameter (LM...) you wanted to modify, press
the r.h. rotary selector again to confirm the setting.
Setting
5 % - 60 %
25 % - 100 %
50 - 150
ON/OFF
1 K – 20 K
ON/OFF
0 °C – 30 °C
40 % - 100 %
0 - 25 min
Factory
range
setting
-
K20
0-3 K
1 K
30 %
70 %
1 - 20
10
93
OFF
1 K
ON
5 °C
70 %
5 - 20
12
2 min
Individual
settings
3063527_201308