Ventilation Unit Parameters; Relay Test; Zone Reset - Wolf BML Operating Instructions Manual

Table of Contents

Advertisement

Control level 3 - Specialist - System parameters
Ventilation unit
parameters
Specialist
Back
Zone designat
LM001
K20
LM015
25 %
LM016
70 %
LM017
10 K
LM018
93
LM023
ON

Relay test

Specialist
LM203
1000
Relay test
Off
Zone designat
Back

Zone reset

Specialist
LM203
1000
Relay test
Off
Zone reset
Back
3063527_201308
The settings can be modified for LM001 to LM204.
See "Specialist parameter list - Overview"
Relay test can be used to activate the outputs for particular
modules.
With the r.h. rotary selector, select the required zone (from
zones 1 to 7) in the "Specialist" menu level (after entering the
code) and press selector to confirm.
Select the "Relay test" parameter and press selector to confirm.
Use the r.h. rotary selector to make your selection (see below)
and press selector to confirm (for relay assignment, see
terminal assignments).
- Rel o.air open
- Rel o.air cl.
- Inverter relay
- Analogue Y1
- Analogue Y2
- Analogue Y3
- Analogue T1
This function can be used to activate the individual outputs
in sequence. When you exit the menu, relay test is disabled
automatically and the system returns to the previously selected
operating mode.
You can use Zone reset to reset all the parameters saved on a
module to their factory settings.
With the r.h. rotary selector, select the required zone (from
zones 1 to 7) in the "Specialist" menu level (after entering the
code) and press selector to confirm.
Select the Zone reset parameter and press selector to confirm.
The following values are reset to their factory settings:
- Zone parameters
- Time program
- Default settings
- Holiday prog
25