Saia-Burgess Controls AG
E.g. the content of MB_PERCO_1 on Panel 1 corresponds to the value "1". In this case, the
value with the symbolic name Example.RoomPanel.Temp.Array_1 will be written.
E.g. the content of MB_PERCO_1 on Panel 2 corresponds to the value "5". In this case, the
value with the symbolic name Example.RoomPanel.Temp.Array_5 will be written.
7.5.4

Container (INT) variable for Room MB Panel

The configuration file UBTERMINAL.TXT is not accessible via the FTP connection because this file
is in the (write-protected) sub-directory / PLC_SYS/CONFIG/.
Containers allow the application program to exchange data with the firmware. All container variables
have the prefix "uBT_". Please note that the variables are case-sensitive!!!
Read/
Internal INT variables
write
(Container)
R/W
uBT_AutoRepeat
No
uBT_BackLight
No
uBT_BackLightOn
PCD7.D443WTxRx | Document 27-644 | Version ENG04 | 2017-10-30
Type
Standard
Min.
value
Min.
length
Boolean
0
0
value string
Boolean
1
0
value string
Boolean
1
0
value string
Max.
Description
value
Max.
length
1
Via Soft Input Panel SIP (on-screen key-
board) Use:
SIP keyboard: AutoRepeat on (1), off (0)
1
Write and read the command of control of
backlighting.
Background lighting is turned off when
the value changes from 1 to 0.
Background lighting is switched on when
the value changes from 0 to 1.
Switching off the background lighting by
uBT_BacklightTimeout does not set this
variable to 0. If the background lighting is
switched on by touching the screen, this
variable is not set to 1.
If the backlight is to be switched off by
means of a push button, the action 'on re-
lease' must be used, and not the function
'on press'.
1
Writing and reading of backlight:
0: Backlight off
1: Backlight on
Permanent writing with 0 or 1 to this vari-
able turns the backlight on or off perma-
nently
For this reason do not write permanently
on this variable but write only once this
variable in case of need.
If the backlight is to be switched off by
means of a push button, the action 'on re-
lease' must be used, and not the function
'on press'.