Temperature Sensor - SBC D443WTPR Manual

Room web panel pcd7.d443wtxrx series
Table of Contents

Advertisement

Saia-Burgess Controls AG
7.5.3

Temperature sensor

The panel features an internal temperature sensor. The temperature value currently measured is
made available in the internal system variable INT uBT_Watch,Temperature,value for the user appli-
cation in Web Editor 8.
Read/
Internal variable INT
write
R
uBT_Watch,Tempera-
ture,value
Calibrating the temperature sensor:
The temperature sensor must be calibrated in the device's Setup Menu when it is used for the first
time.
To do this, you need to open the panel's Setup Menu as described in Chapter 5.3.5.
In Setup Menu -> System -> Special -> Calibration, a correction value for the installation location
must be defined.
To do this, you need to measure the temperature at the installation location using an external
measuring device. The temperature value measured must be entered in the Setup Menu. The cor-
rection factor is calculated and saved by the device itself.
IMPORTANT:
To ensure that the system functions correctly, the installation location must be taken into account
when using the temperature sensor as described in Chapter 1.5.1.
PCD7.D443WTxRx | Document 27-644 | Version ENG04 | 2017-10-30
Type
Standard
Min.
value
Min.
length
Type
Current
Max.
Description
value
Max.
length
Read the temperature DEC
uBT_Watch,Temperature,value
Temperature resolution is 0.1°C.
21.3°C gives the value 21.3 in the inter-
nal variable.
If the value is transferred to the PCD, the
format "DEC1" must be selected in the
Web Editor.
As a result, the value is stored as 213 in
the PCD.
38

Advertisement

Table of Contents
loading

Table of Contents