Setting guidelines

There are two settings related to the IEC 61850–8–1 protocol:
Operation: User can set IEC 61850 communication to On or Off.
GOOSEPortEd1: Selection of the Ethernet link where GOOSE traffic shall be sent
and received. This is only valid for Edition 1 and can be ignored if Edition 2 is
used. For Edition 2, the Ethernet link selection is done with the Ethernet
Configuration Tool (ECT) in PCM600.

Horizontal communication via GOOSE

Sending data

In addition to the data object and data attributes of the logical nodes, it is possible
to send the outputs of the function blocks using the generic communication blocks.
The outputs of this function can be set in a dataset and be sent in a GOOSE Control
Block to other subscriber IEDs. There are different function blocks for different
type of sending data.
Generic communication function for Single Point indication SPGAPC,
SP16GAPC
Application
Generic communication function for Single Point Value (SPGAPC) function is
used to send one single logical output to other systems or equipment in the
substation. SP16GAPC can be used to send up to 16 single point values from the
application functions running in the same cycle time. SPGAPC has one visible
input and SPGAPC16 has 16 visible inputs that should be connected in the ACT
tool.
Setting guidelines
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
Application
Generic communication function for measured values (MVGAPC) function is used
to send the instantaneous value of an analog signal to other systems or equipment
in the substation. It can also be used inside the same IED, to attach a RANGE
aspect to an analog value and to permit measurement supervision on that value.
Setting guidelines
The settings available for Generic communication function for Measured Value
(MVGAPC) function allows the user to choose a deadband and a zero deadband for
the monitored signal. Values within the zero deadband are considered as zero.