ABB RET650 Applications Manual page 95

Relion 650 series, transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

1MRK 504 169-UEN A
Transformer protection RET650 2.2 IEC
Application manual
Setting parameter
LocationOLTC1
Other Parameters
1)
To compensate for delta connected CTs
2)
Zero-sequence current is already removed by connecting main CTs in delta
Delta-star connected power transformer without tap charger
Single line diagrams for two possible solutions for such type of power transformer
with all relevant application data are given in figure 33.
CT 400/5
Star
60 MVA
115/24.9 kV
Dyn1
(D
Y)
AB
CT 1500/5
Star
IEC06000555 V1 EN-US
Figure 33:
Two differential protection solutions for delta-star connected power
transformer
For this particular power transformer the 115 kV side phase-to-earth no-load
voltages lead by 30° the 24.9 kV side phase-to-earth no-load voltages. Thus when
external phase angle shift compensation is done by connecting main 24.9 kV CTs
in delta, as shown in the right-hand side in figure 33, it must be ensured that the
24.9 kV currents are rotated by 30° in anti-clockwise direction. Thus, the DAB CT
delta connection (see figure 33) must be used for 24.9 kV CTs in order to put
115 kV & 24.9 kV currents in phase.
Select value for solution 1 (star
connected CT)
Not used
Not relevant for this application.
Use default value.
60 MVA
115/24.9 kV
Dyn1
(D
AB
CT 1500/5
Section 6
Differential protection
Selected value for solution 2
(delta connected CT)
Not used
Not relevant for this
application. Use default
value.
SEMOD167854-209 v4
CT 400/5
Star
Y)
in Delta
(DAB)
en06000555.vsd
89