Application - ABB RET650 Applications Manual

Relion 650 series, transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 12
Logic
12.12.2
12.12.3
12.13
12.13.1
262

Application

The function TEIGAPC is used for user-defined logics and it can also be used for
different purposes internally in the IED. An application example is the integration
of elapsed time during the measurement of neutral point voltage or neutral current
at earth-fault conditions.
Settable time limits for warning and alarm are provided. The time limit for
overflow indication is fixed to 999999.9 seconds.
Setting guidelines
The settings tAlarm and tWarning are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the
range
1.00 second ≤ tAlarm ≤ 99 999.99 seconds
1.00 second ≤ tWarning ≤ 99 999.99 seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit
float representation
99 999.99 seconds < tAlarm ≤ 999 999.0 seconds
99 999.99 seconds < tWarning ≤ 999 999.0 seconds
Note that tAlarm and tWarning are independent settings, that is,
there is no check if tAlarm > tWarning.
The limit for the overflow supervision is fixed at 999999.9 seconds.
Comparator for integer inputs - INTCOMP
Identification
Function description
Comparison of integer values
IEC 61850
IEC 60617
identification
identification
INTCOMP
Int<=>
Transformer protection RET650 2.2 IEC
1MRK 504 169-UEN A
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v2
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
ANSI/IEEE C37.2
device number
Application manual