ABB RET650 Applications Manual page 293

Relion 650 series, transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

1MRK 504 169-UEN A
Transformer protection RET650 2.2 IEC
Application manual
It is possible to handle up to 40 analog and 352 binary signals, either internal
signals or signals coming from external inputs. The binary signals are identical in
all functions that is, Disturbance recorder (DR), Event recorder (ER), Indication
(IND), Trip value recorder (TVR) and Event list (EL) function.
User-defined names of binary and analog input signals is set using PCM600. The
analog and binary signals appear with their user-defined names. The name is used
in all related functions (Disturbance recorder (DR), Event recorder (ER), Indication
(IND), Trip value recorder (TVR) and Event list (EL)).
Figure
100
shows the relations between Disturbance report, included functions and
function blocks. Event list (EL), Event recorder (ER) and Indication (IND) uses
information from the binary input function blocks (BxRBDR). Trip value recorder
(TVR) uses analog information from the analog input function blocks (AxRADR),
which is used by Fault locator (FL) after estimation by Trip Value Recorder (TVR).
Disturbance report function acquires information from both AxRADR and
BxRBDR.
Analog signals
Binary signals
IEC09000336 V3 EN-US
Figure 100:
Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also
influences the sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick
status information about the IED.
AxRADR
DRPRDRE
Trip value rec
Disturbance
BxRBDR
recorder
Event list
Event recorder
Indications
Section 13
Monitoring
Disturbance Report
FL
Fault locator
IEC09000336-3-en.vsdx
287