ABB RET650 Applications Manual page 279

Relion 650 series, transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

1MRK 504 169-UEN A
Transformer protection RET650 2.2 IEC
Application manual
The available measured values of an IED are depending on the
actual hardware (TRM) and the logic configuration made in
PCM600.
Measurement function application for a 400kV OHL
Single line diagram for this application is given in figure 97:
400kV Busbar
1000/1 A
400
0
1 ,
/
kV
3
3
P
Q
400kV OHL
IEC09000039-1-EN V3 EN-US
Figure 97:
Single line diagram for 400kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as
indicated in figure
97
it is necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel
PhaseAngleRef (see Section
PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
general settings as shown in table 33.
level supervision of active power as shown in table 34.
calibration parameters as shown in table 35.
IED
IEC09000039-3-en.vsdx
"Setting of the phase reference
Section 13
Monitoring
SEMOD54481-12 v11
channel") using