Transformer protection RET650 2.2 IEC
Application manual
Metering

Pulse-counter logic PCFCNT

Identification
Function description
Pulse-counter logic
Application
Pulse-counter logic (PCFCNT) function counts externally generated binary pulses,
for instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module (BIM),
and read by the PCFCNT function. The number of pulses in the counter is then
reported via the station bus to the substation automation system or read via the
station monitoring system as a service value. When using IEC 61850–8–1, a scaled
service value is available over the station bus.
The normal use for this function is the counting of energy pulses from external
energy meters. An optional number of inputs from an arbitrary input module in
IED can be used for this purpose with a frequency of up to 40 Hz. The pulse-
counter logic PCFCNT can also be used as a general purpose counter.
Setting guidelines
Parameters that can be set individually for each pulse counter from PCM600:
Operation: Off/On
tReporting: 0-3600s
EventMask: NoEvents/ReportEvents
Configuration of inputs and outputs of PCFCNT is made via PCM600.
IEC 61850
IEC 60617
identification
identification
PCFCNT
S00947 V1 EN-US
Section 14
Metering
IP14600-1 v3
M14879-1 v4
ANSI/IEEE C37.2
device number
-
M13395-3 v6
M13396-4 v9