ABB RET650 Applications Manual page 278

Relion 650 series, transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 13
Monitoring
13.1.4.1
272
All phase angles are presented in relation to defined reference channel. The
parameter PhaseAngleRef defines the reference, see Section
Calibration curves
It is possible to calibrate the functions (, CMMXU, VMMXU and VNMMXU) to
get class 0.5 presentations of currents, voltages and powers. This is accomplished
by amplitude and angle compensation at 5, 30 and 100% of rated current and
voltage. The compensation curve will have the characteristic for amplitude and
angle compensation of currents as shown in figure
will be used as reference channel and compared with the curve for calculation of
factors. The factors will then be used for all related channels.
IEC05000652 V2 EN-US
Figure 96:
Calibration curves
Setting examples
Three setting examples, in connection to Measurement function (), are provided:
Measurement function () application for a OHL
Measurement function () application on the secondary side of a transformer
Measurement function () application for a generator
For each of them detail explanation and final list of selected setting parameters
values will be provided.
1MRK 504 169-UEN A
"Analog
inputs".
96
(example). The first phase
Transformer protection RET650 2.2 IEC
Application manual
SEMOD54481-4 v5