ABB RET650 Applications Manual page 266

Relion 650 series, transformer protection
Hide thumbs Also See for RET650:
Table of Contents

Advertisement

Section 12
Logic
12.11
12.11.1
12.11.2
260
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
IN11
BOOLEAN
IN12
BOOLEAN
IN13
BOOLEAN
IN14
BOOLEAN
IN15
BOOLEAN
IN16
BOOLEAN
The sum of the numbers in column "Value when activated" when all INx (where
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can
be converted to an integer by the IB16 function block.
Integer to Boolean 16 conversion with logic node
representation ITBGAPC
Identification
Function description
Integer to boolean 16 conversion with
logic node representation
Application
Integer to boolean 16 conversion with logic node representation function
(ITBGAPC) is used to transform an integer into a set of 16 boolean signals.
ITBGAPC function can receive an integer from a station computer – for example,
over IEC 61850–8–1. This function is very useful when the user wants to generate
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
0
Input 10
0
Input 11
0
Input 12
0
Input 13
0
Input 14
0
Input 15
0
Input 16
IEC 61850
ANSI/IEEE C37.2
identification
device number
ITBGAPC
Transformer protection RET650 2.2 IEC
1MRK 504 169-UEN A
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0
1024
0
2048
0
4096
0
8192
0
16384
0
32768
0
SEMOD158419-1 v3
SEMOD167944-2 v4
-
-
SEMOD158512-5 v7
Application manual