Level E - Calibration - ABB COMMANDER 351 User Manual

Table of Contents

Advertisement

...4 CONFIGURATION MODE
...4.10 Level E – Calibration
FCAL
MAN
E11
Fb. L O
100. 0
E. 1 2
Fb. H I
500. 0
rEF
2700
FCAL
NO
O. C AL
NO
Fb. H I
500
E. 1 3
rEF
2700
E. 1 4
bEtA
3977
E. 1 5
CJ1
25. 2
E. 1 6
CJ3
25. 2
LEV. E
CAL
•1
Displayed only if Motorized Valve with feedback output type is selected – see Section 4.2, Basic Configuration.
•2
Displayed only if corresponding input type is set to 'THC'.
70
•1
Position Feedback Electrical Range Low
Set the minimum electrical input value.
[0.0 to 999.9]
For resistance input types, no decimal places are displayed. For all other
input types, 1 decimal place is displayed.
•1
Position Feedback Electrical Range High
Set the maximum electrical input value.
[0.0 to 999.9]
Continued in
Cold Junction Reference Value
This value should only be changed if a new CJ sensor is supplied with a
CJ reference value different to 2700.
The resistance (in Ohms) of the CJ sensor at 25°C.
Cold Junction Beta Value
This value should only be changed if a new CJ sensor is supplied with a
CJ Beta value different to 3977.
The beta value of the CJ sensor.
Cold Junction Reading – I/P1 and I/P2
The temperature measured by the cold junction sensor is displayed in °C.
•2
Cold Junction Reading – I/P3
The temperature measured by the cold junction sensor is displayed in °C.
Return to top of Calibration Level.
Cold Junction Reference Value
E.11...E.16
frame.