4.5 Level 9 – Set Point Configuration
Note. Level 9 is not applicable when an Indicator template (templates 7 and 8) or an Auto/Manual station
template (templates 3 and 4) is selected.
9. 0 0
LEV9
SEt. P
9. 0 1
trCK
OFF
9. 0 2
SPt. H
1000
9. 0 3
SPt. L
0
•1
Only available if a remote set point template is selected.
4 CONFIGURATION MODE...
Level 9 – Set Point Configuration
Note. To select this frame from anywhere in this page, press and
hold the
key for a few seconds.
Set Point Tracking Enable
L
o
c
D
s i
p
a l
y
O
F
F
L
O
C
r
E
M
L
-
r
Local Set Point Tracking
when manual mode is selected.
Remote Set Point Tracking
when in remote set point mode. If the controller is put into manual mode
the set point reverts from remote to local.
Set Point Limits
The set point limits define the maximum and minimum values to which
the local and/or remote set points can be adjusted.The set point limits do
not apply when in Manual mode with local set point tracking enabled. If
the set point is outside its limits when Automatic mode is selected, the set
point value can only be adjusted towards its limits. Once within the limits
they apply as normal.
Control Set Point (CSPT) High Limit
[–999 to 9999 in engineering units]
Control Set Point (CSPT) Low Limit
[–999 to 9999 in engineering units]
Note. Operator level adjustment of the set point can be disabled –
see Section 4.7, Operator Configuration/ Set Point Adjustment Enable.
Continued...
l a
S
t e
P
i o
t n
R
T
a r
c
k
n i
g
O
F
F
O
N
O
F
F
O
N
– the local set point tracks the process variable
– local set point tracks the remote set point
9.00...9.03
e
m
o
e t
S
t e
P
i o
t n
T
a r
c
k
n i
g
O
F
F
O
F
F
O
N
1 •
O
N
1 •
51

Advertisement

Table of Contents
loading

Table of Contents