...3.2 Level 2 – Tune
2. . . 2 2
Y1. S t
50. 0
2. . . 2 3
Y2. S t
50. 0
LEV2
tUNE
•1 Displayed only if a Heat/Cool output type is selected – see Section 4.2, Basic Configuration/ Output
Type.
•1
Heat/Cool Output 1 Start
This parameter defines the PID output value above which
Output 1 (heat) becomes active.
[0.0 to 100.0%]
100%
Output 2
0%
0%
Heat/Cool Output 2 Start
•1
This parameter defines the PID output value below which Output
2 (cool) becomes active.
[0.0 to ≤ Y1st %] – see Heat/Cool Output 1
Return to top of page
Reverse-direct
or direct-reverse
Output 1
100%
Y2. S t
Y1. S t
PID Output
3 SET UP MODE...
Reverse-reverse
or direct-direct
100%
Output 2
0%
0%
Y2. S t
Y1. S t
PID Output
8
2.22...2.23
Output 1
100%
31