Specifications - DSC T-LINK TL250 Installation Manual

Network internet alarm communicator
Hide thumbs Also See for T-LINK TL250:
Table of Contents

Advertisement

Mode 5: DVACS®* Mode (V1.10 or later)(TL250 only)
In DVACS mode, the system is configured as a communicator with a compatible DVACS
alarm panel. Refer to section 6 for details. Refer to appendix C for a list of compatible
DVACS panels and modules.
NOTE: T-Link TL250 zone events are transmitted using the standard T-Link SIA protocol.
DVACS generated events are transmitted using the DVACS protocol.
NOTE: DVACS Mode 5 is used in ULC listed installations.
*
DVACS is a registered trademark of Electro Arts Ltd. Scarborough Ontario, Canada
1.2
Specifications/Requirements
The maximum allowable current draw from a compatible DSC panel on the Aux terminal
Output is 500 mA @ 12V
T-Link TL250 module has 2 switched negative programmable outputs (50 mA @ 12 V
Input Voltage:12 V
Input Current: T-LINK TL250 Max current draw: 275mA
Dimensions: 3.25" × 5.25" (8.3 cm × 13.3 cm)
Operating Temperature: 32°-122°F (0°-49°C)
Output Protocols: UDP/IP 10/100 BaseT half duplex, TCP/IP for Console and DLS commu-
nications
Input Protocols: PC-Link (SIA format), DVACS (V1.10 and higher), Contact ID protocol.
(TL300 Only)
Digital Inputs: 4-digital inputs (can be increased to 12 using the PC5108)
Connectors: 4-pin header for the PC-Link and RJ-45 for Ethernet, DVACS adaptor
(DVACS kit only)
Programming: Panel keypad, console on the RS232 or remote T-Link console.
Network: Ethernet LAN/WAN 10 BaseT or 10/100 BaseT
E-mail: sends alarm messages to maximum 2 E-mail addresses
(NOT available for DVACS installations)
Downloading Support for DSC Panels:DLS-3 and/or System Administrator software
Multiple Central Stations: primary and backup via phone line*
(NOT available for DVACS installations).
Call Direction Options: primary or backup communicator using panel call direction
(NOT available for DVACS installations).
Approval Listings: FCC, IC, CE
UL (Grade of Service AA, Encrypted Line Security)
ULC (Signal Channel Security Level 4/5)
*NOTE:This manual shall be used with the Installation Manual of the associated Alarm Con-
troller for installation.
NOTE: For UL Listed fire installations, shared on-premises communication equipment is
required to be UL Listed for Information Technology Equipment. The communication medium
between protected property and communications service provider must be for the exclusive
use of the protected property and not shared with other communications service provider
subscriber.
NOTE:When a hub or router/gateway is used on the premises with the T-Link TL250, 24-hr.
standby power is required for these devices (i.e., UL listed UPS, battery backup).
NOTE:This equipment (T-Link TL250) shall be installed and used within an environment that
provides the POLLUTION DEGREE MAX 2 and OVERVOLTAGES CATEGORY II NON-HAZARD-
OUS LOCATIONS, indoor only. The equipment must be FIXED and permanently connected,
and is intended to be installed by SERVICE PERSONS (i.e., having the appropriate technical
training and experience necessary to be aware of hazards which that person may be exposed
to in performing the task, and of measures to minimize the risks to that person or other per-
sons).
Ethernet communication lines must be connected to an approved (acceptable to local author-
ities) type NID (Network Interface Device) before leaving the premises (e.g., UL installations,
UL60950 Listed NID).
. Operational current draw of the T-Link TL250 is 250 mA. The
DC
DC
T-LINK TL300 Max current draw: 360mA

Specifications

CAUTION
2
).
DC

Advertisement

Table of Contents
loading

This manual is also suitable for:

T-link tl350