Panel Mounting; Technical Specifications; Ratings Compatibility - DSC PowerSeries Neo 3G2080E Installation Manual

Cellular alarm communicator, internet and hspa dual-path alarm communicator, internet alarm communicator
Hide thumbs Also See for PowerSeries Neo 3G2080E:
Table of Contents

Advertisement

The following communicators are compatible with HS2016, HS2016-4, HS2032, HS2064, and HS2128 panels:
3G2080(R)E (HSPA(3G)/GPRS only)
l
TL2803G(R)E (Ethernet/Internet + HSPA(3G)/GPRS dual-path)
l
TL280(R)E (Ethernet/Internet only)
l
128-bit AES encryption via cellular and Ethernet/Internet (NIST validation cert. number 2645).
l
Back up or primary cellular alarm communication.
l
Automatically switches to 2G (EDGE/GPRS) if HSPA(3G) service is not available.
l
Ethernet LAN/WAN 10/100 BASE-T (TL2803G(R)E and TL280(R)E only).
l
Fully redundant Ethernet/Internet and cellular dual-path alarm communication (TL2803G(R)E only).
l
Full event reporting to central station.
l
Individual Internet and/or cellular periodic test transmission.
l
Integrated call routing.
l
Visual Verification (Requires Sur-Gard System 5 Receiver)
l
Remote firmware upgrade capability of the communicator and panel firmware via Ethernet and/or cellular.
l
Panel remote uploading/downloading support via cellular and Ethernet/Internet.
l
PC-LINK connection.
l
Programmable labels.
l
SIA and Contact ID (CID) formats supported.
l
Signal strength and trouble display LEDs.
l
Supervision heartbeats sent via cellular and Ethernet/Internet.
l
Third party integration over cellular/IP. The product supports third party application via serial (R-models only), cellular and,
l
Ethernet. Refer to third-party application documentation for more information.
The TL2803G(R)E is also suitable to be used with a compatible control unit listed for dual line security transmission when used
in conjunction with a DACT or a Public Switched Data Network (PSDN) transmitter, where the PSDN provides the line security
and is the primary line. In this mode, alarm signals are to be sent simultaneously over both communication methods.
For EN50131-1 compliant installations, the following programming options shall be set as described.
[382] enable option 5 (YES) this will enable Alternate communicator
l
Supervision Heartbeat (required for ATS4 and ATS5):
[851][004] set to 0087h (135s heartbeat).
l
NOTE: The compatible receiver at ARC location shall have supervision window programmed for 1800s (ATS4) or 180s
(ATS5).
[851][005] options 1,2 and 3 shall be enabled
l
[851][005] option 8 shall be enabled
l
Test transmission (required for ATS3):
[851] System test options [026-029] shall be enabled (FF) for the communication paths available.
l
[851][124-125] and [224-225] shall be programmed with time of day for test transmission and 1440 minutes (24h) for test
l
transmission cycle
Configuration of communication paths (all ATS classes)
[300][001] select option 02 for auto routing (this will allow transmission of the events over all available communication
l
paths in the system)
[380] enable option 5 (YES) for parallel transmission over all available communication paths (if redundant configuration is
l
desired)
[384] enable the desired back-up configuration (receiver 2 back-up for receiver 1 or receiver 3 back-up for receiver 1).
l
Model
Power Supply Ratings
Input Voltage

Panel Mounting

Technical Specifications

EN50131-1 Installation Requirements

Ratings Compatibility

Table 1: Communicator Ratings
3G2080(R)E
Cellular only
Features
TL280(R)E
Internet only
10.8-12.5 VDC
4
TL2803G(R)E
Internet and Cellular