CHAPTER 5: SETTINGS
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
5.5.5 FlexLogic equation editor
SETTINGS FLEXLOGIC FLEXLOGIC EQUATION EDITOR
FLEXLOGIC
EQUATION EDITOR
There are 1,024 FlexLogic entries available, numbered from 1 to 1024, with default END entry settings. If a "Disabled"
element is selected as a FlexLogic entry, the associated state flag is never set to '1'. Press the +/– key when editing
FlexLogic equations to quickly scan through the major parameter types.
5.5.6 FlexLogic timers
SETTINGS FLEXLOGIC FLEXLOGIC TIMERS FLEXLOGIC TIMER 1(32)
FLEXLOGIC
TIMER 1
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
— Selects the time measurement unit.
TIMER 1 TYPE
— Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 PICKUP DELAY
— Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY
5.5.7 Non-volatile latches
SETTINGS FLEXLOGIC NON-VOLATILE LATCHES LATCH 1(16)
LATCH 1
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC ENTRY 1:
END
FLEXLOGIC ENTRY 1024:
END
TIMER 1
TYPE: millisecond
TIMER 1 PICKUP
DELAY:
0
TIMER 1 DROPOUT
DELAY:
0
LATCH 1
FUNCTION: Disabled
LATCH 1 ID:
NV Latch 1
LATCH 1 TYPE:
Reset Dominant
LATCH 1 SET:
Off
LATCH 1 RESET:
Off
LATCH 1
TARGET: Self-reset
LATCH 1
EVENTS: Disabled
Range: FlexLogic operands
Range: FlexLogic operands
Range: millisecond, second, minute
Range: 0 to 60000 in steps of 1
Range: 0 to 60000 in steps of 1
Range: Disabled, Enabled
Range: up to 20 alphanumeric characters
Range: Reset Dominant, Set Dominant
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
FLEXLOGIC
5