TARGETS MENU
•
How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five
seconds.
•
What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If a
module has intentionally been added or removed, refresh the order code under Device Setup. If the problem persists,
contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail
•
Latched target message: No.
•
Description of problem: A FlexLogic equation is incorrect.
•
How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified
•
What to do: Finish all equation editing and use self tests to debug any errors.
UNIT NOT PROGRAMMED:
Check Settings
•
Latched target message: No.
•
Description of problem: The
programmed.
•
How often the test is performed: On power up and whenever the
setting is altered
•
What to do: Program all settings and then set
DIAGNOSTIC FAILURE___:
Self Test Error
•
Latched target message: No.
•
Description of problem: Internal recovery failure detected.
•
How often the test is performed: Continuous.
•
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
SYSTEM FAILURE___:
with 2nd line detail
7
•
Latched target message: Yes.
•
Description of problem: Module hardware failure detected.
•
How often the test is performed: Module dependent.
•
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
7.2.2.3 Minor self-test error messages
Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
DIAGNOSTIC ALARM:
with 2nd line detail
•
Latched target message: Yes.
•
Description of problem: Internal process disruption detected.
•
How often the test is performed: Module dependent.
7-6
PRODUCT SETUP INSTALLATION RELAY SETTINGS
.
PRODUCT SETUP INSTALLATION RELAY SETTINGS
PRODUCT SETUP INSTALLATION RELAY SETTINGS
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: COMMANDS AND TARGETS
setting indicates the B90 is not
to "Programmed."
.