User-Programmable Fault Report - GE B90 Instruction Manual

Low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

PRODUCT SETUP
The B90 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B
signals. UTC time is provided by SNTP servers.
The real-time clock (RTC) and time stamps reported in historical records and communication protocols can be incorrect if
the Local Time settings are not configured properly.
See the IRIG-B section in the Installation chapter for guidance on these settings when using an IRIG-B source that sets the
IRIG-B control bits according to IEEE Std 1344-1995.
LOCAL TIME OFFSET FROM UTC
zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative values. A value
of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is synchronized with a
communications protocol providing only local time or it is free-running, the offset setting is used to calculate UTC from the
local time these provide. When the RTC is synchronized with a communications protocol providing only UTC (such as PTP or
SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time.
DAYLIGHT SAVINGS TIME
when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and
so the DST settings are ignored.

5.3.9 User-programmable fault report

SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE FAULT REPORTS  USER-PROGRAMMABLE FAULT REPORT
1(2)
 USER-PROGRAMMABLE
 FAULT REPORT 1
5
When enabled, this function monitors the pre-fault trigger. The pre-fault data are stored in the memory for prospective
creation of the fault report on the rising edge of the pre-fault trigger. The element waits for the fault trigger as long as the
pre-fault trigger is asserted, but not shorter than 1 second. When the fault trigger occurs, the fault data is stored and the
complete report is created. If the fault trigger does not occur within 1 second after the pre-fault trigger drops out, the
element resets and no record is created.
The user programmable record contains the following information: the user-programmed relay name, detailed firmware
revision (x.xx, for example) and relay model (B90), the date and time of trigger, the name of pre-fault trigger (a specific
FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the
active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger),
and fault values of all programmed analog channels (at the fault trigger).
Each fault report is stored as a file to a maximum capacity of ten files. An eleventh trigger overwrites the oldest file. The
EnerVista software is required to view all captured data. A FAULT RPT TRIG event is automatically created when the report
is triggered.
The relay includes two user-programmable fault reports to enable capture of two types of trips (for example, trip from
thermal protection with the report configured to include temperatures, and short-circuit trip with the report configured to
include voltages and currents). Both reports feed the same report file queue.
The last record is available as individual data items via communications protocols.
5-104
— Used to specify the local time zone offset from UTC (Greenwich Mean Time) in hours. Time
and
— Can be used to allow the relay to follow the DST rules of the local time zone. Note that
DST
FAULT REPORT 1
FUNCTION: Disabled
PRE-FAULT 1 TRIGGER:
Off
FAULT 1 TRIGGER:
Off
FAULT REPORT 1 # 1:
Off
FAULT REPORT 1 #32:
Off
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: Off, any actual value analog parameter
Range: Off, any actual value analog parameter
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS