GROUPED ELEMENTS

5.6.4 Breaker failure (ANSI 50BF)

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  BREAKER FAILURE 1(24)
 BREAKER FAILURE
5
5-160
 BREAKER FAILURE
 CURRENT SUPV 1
 BREAKER FAILURE 1
BF1 CURRENT SUPV
FUNCTION: Disabled
BF1 CT:
F1
BF1 AMP SUPV
PICKUP: 1.050 pu
BF1 AMP HISET
PICKUP: 1.050 pu
BF1 AMP LOSET
PICKUP: 1.050 pu
BF1 FUNCTION:
Disabled
BF1 INITIATE:
Off
BF1 USE AMP SUPV:
Yes
BF1 USE SEAL-IN:
Yes
BF1 AMP SUPV OP A:
Off
BF1 AMP SUPV OP B:
Off
BF1 AMP SUPV OP C:
Off
BF1 USE TIMER 1:
Yes
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 2:
Yes
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 3:
Yes
BF1 TIMER 3 PICKUP
DELAY: 0.000 s
BF1 BKR POS1:
Off
BF1 BKR POS2:
Off
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: Disabled, Enabled
Range: Available current channels
Range: 0.020 to 30.000 pu in steps of
0.001
Range: 0.020 to 30.000 pu in steps of
0.001
Range: 0.020 to 30.000 pu in steps of
0.001
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Yes, No
Range: Yes, No
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Yes, No
Range: 0.000 to 65.535 s in steps of
0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of
0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of
0.001
Range: FlexLogic operand
Range: FlexLogic operand