PRODUCT SETUP
Change remote passwords
Proper passwords are required to enable each command or setting level access, which are explained in the previous
section.
SETTINGS  PRODUCT SETUP  SECURITY  CHANGE REMOTE PASSWORDS
 CHANGE REMOTE
 PASSWORDS
To set the command or setting password in EnerVista:
1.
In the EnerVista software or from the front panel, navigate to Settings > Product Setup > Security menu item to open
the remote password settings window.
2.
Click the command or setting password Change button.
3.
Enter the new password in the New Password field. Requirements are outlined in the Password Requirements section
earlier in this chapter. When an original password has already been used, enter it in the Enter Password field and click
the Send Password to Device button.
4.
Re-enter the password in the Confirm Password field.
5.
Click the OK button. The password is checked to ensure that it meets requirements.
5
If you establish a local (serial) connection to the relay, you cannot view remote passcodes.
Access supervision
SETTINGS  PRODUCT SETUP  SECURITY  ACCESS SUPERVISION
 ACCESS
 SUPERVISION
The following access supervision settings are available.
INVALID ATTEMPTS BEFORE LOCKOUT
within a three-minute time span before lockout occurs. When lockout occurs, the
FlexLogic operands are set to "On." These operands are returned to the "Off" state upon expiration of the lockout.
DENIED
PASSWORD LOCKOUT DURATION
of invalid password entries specified by the
5-8
CHANGE SETTING
PASSWORD: No
CHANGE COMMAND
PASSWORD: No
 ACCESS LEVEL
 TIMEOUTS
INVALID ATTEMPTS
BEFORE LOCKOUT: 3
PASSWORD LOCKOUT
DURATION: 5 min
— This setting specifies the number of times that an incorrect password can be entered
— This setting specifies the time that the B90 locks out password access after the number
INVALID ATTEMPTS BEFORE LOCKOUT
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: No, Yes
Range: No, Yes
See below
Range: 2 to 5 in steps of 1
Range: 5 to 60 minutes in steps of 1
or
LOCAL ACCESS DENIED
setting has occurred.