Flex States; Ethernet; Real Time Clock Synchronizing - GE B90 Instruction Manual

Low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

STATUS

6.3.9 Flex States

ACTUAL VALUES  STATUS  FLEX STATES
 FLEX STATES
There are 256 FlexState

6.3.10 Ethernet

ACTUAL VALUES  STATUS  ETHERNET
 ETHERNET
These values indicate the status of the first, second, and third Ethernet links.

6.3.11 Real time clock synchronizing

ACTUAL VALUES  STATUS  REAL TIME CLOCK SYNCHRONIZING
 REAL TIME CLOCK
 SYNCHRONIZING
6
actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
RTC SYNC SOURCE
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, Other, and None, where "Other" means any less precise source (SNTP,
IEC 103, IEC 104, or DNP). An actual value displays when the relay includes the IEEE 1588 software option.
The
GRANDMASTER ID
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
ACCURACY
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
6-6
PARAM 1: Off
Off
PARAM 256: Off
Off
TM
bits available. The second line value indicates the state of the given FlexState bit.
ETHERNET PRI LINK
STATUS: Fail
ETHERNET SEC LINK
STATUS: Fail
ETHERNET TER LINK
STATUS: Fail
RTC SYNC SOURCE:
None
GRANDMASTER ID:
0X0000000000000000
ACCURACY:
999999999 ns
PORT 1 PTP STATE:
No Signal
PORT 2 PTP STATE:
No Signal
PORT 3 PTP STATE:
No Signal
PTP - IRIG-B DELTA:
500000000 ns
is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
Range: On, Off
Range: On, Off
Range: Fail, OK
Range: Fail, OK
Range: Fail, OK
Range: see below
Range: any 8 octet value
Range: 0 to 999,999,999 ns
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: -500,000,000 to +500,000,000 ns
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES