User-Programmable Fault Report - GE t60 Instruction Manual

Ur series transformer protection system
Hide thumbs Also See for t60:
Table of Contents

Advertisement

5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 FAULT REPORT 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
When enabled, this function monitors the pre-fault trigger. The pre-fault data are stored in the memory for prospective cre-
ation of the fault report on the rising edge of the pre-fault trigger. The element waits for the fault trigger as long as the pre-
fault trigger is asserted, but not shorter than 1 second. When the fault trigger occurs, the fault data is stored and the com-
plete report is created. If the fault trigger does not occur within 1 second after the pre-fault trigger drops out, the element
resets and no record is created.
The user programmable record contains the following information: the user-programmed relay name, detailed firmware
revision (7.0x, for example) and relay model (T60), the date and time of trigger, the name of pre-fault trigger (a specific
FlexLogic operand), the name of fault trigger (a specific FlexLogic operand), the active setting group at pre-fault trigger, the
active setting group at fault trigger, pre-fault values of all programmed analog channels (one cycle before pre-fault trigger),
and fault values of all programmed analog channels (at the fault trigger).
The report includes fault duration times for each of the breakers (created by the breaker arcing current feature). To include
fault duration times in the fault report, the user must enable and configure breaker arcing current feature for each of the
breakers. Fault duration is reported on a per-phase basis.
Each fault report is stored as a file to a maximum capacity of ten files. An eleventh trigger overwrites the oldest file. The
EnerVista UR Setup software is required to view all captured data. A
the report is triggered.
The relay includes two user-programmable fault reports to enable capture of two types of trips (for example, trip from ther-
mal protection with the report configured to include temperatures, and short-circuit trip with the report configured to include
voltages and currents). Both reports feed the same report file queue.
The last record is available as individual data items via communications protocols.
PRE-FAULT 1 TRIGGER: Specifies the FlexLogic operand to capture the pre-fault data. The rising edge of this oper-
and stores one cycle-old data for subsequent reporting. The element waits for the fault trigger to actually create a
record as long as the operand selected as
element resets and no record is created.
FAULT 1 TRIGGER: Specifies the FlexLogic operand to capture the fault data. The rising edge of this operand stores
the data as fault data and results in a new report. The trigger (not the pre-fault trigger) controls the date and time of the
report.
FAULT REPORT 1 #1 to FAULT REPORT 1 #32: These settings specify an actual value such as voltage or current
magnitude, true RMS, phase angle, frequency, temperature, etc., to be stored should the report be created. Up to 32
channels can be configured. Two reports are configurable to cope with variety of trip conditions and items of interest.
GE Multilin


USER-PROGRAMMABLE FAULT REPORT

FAULT REPORT 1
FUNCTION: Disabled
PRE-FAULT 1 TRIGGER:
Off
FAULT 1 TRIGGER:
Off
FAULT REPORT 1
#1:
Off
FAULT REPORT 1
#2:
Off
FAULT REPORT 1
#3:
Off
FAULT REPORT 1 #32:
Off
PRE-FAULT 1 TRIGGER
T60 Transformer Protection System
5.2 PRODUCT SETUP
5.2.8 USER-PROGRAMMABLE FAULT REPORT
USER-PROGRAMMABLE FAULT REPORT 1(2)
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: Off, any actual value analog parameter
Range: Off, any actual value analog parameter
Range: Off, any actual value analog parameter
Range: Off, any actual value analog parameter
event is automatically created when
FAULT RPT TRIG
is "On". If the operand remains "Off" for 1 second, the
5