YASKAWA J1000 CIMR-JC series Quick Start Manual page 35

Compact v/f control drive
Hide thumbs Also See for J1000 CIMR-JC series:

Advertisement

L1-02 Motor Overload Protection Time
Setting Range: 0.1 to 5.0 Minutes
Factory Default: 1.0 Minutes
The L1-02 parameter will set the allowed operation time before the oL1 fault will occur
when the drive is running at 60 Hz and 150% of the motor's full load amp rating (E2-01).
Adjusting the value of L1-02 can shift the set of oL1 curves up the Y-axis of the diagram
below but will not change the shape of the curves.
Figure 2
Operation time (minutes)
10
7
3
1
0.4
0.1
0
YASKAWA ELECTRIC TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
100
150
Figure 3 Motor Overload Protection Time
8 Instructions for UL and cUL
Cold start
Hot start
Motor current (%)
200
E2-01 = 100% motor current
EN 35