Power On
Before turning on the power supply,
• Make sure all wires are connected properly.
• Make sure no screws, loose wire ends or tools are left in the drive.
• After turning the power on, the drive mode display should appear and no fault or alarm
should be displayed.
Normal / Heavy Duty Selection (C6-01)
The drive supports two ratings, Normal Duty and Heavy Duty. Both have different output
current ratings (refer to the catalog or instruction manual). Set the Duty mode in accordance
with the application.
Mode
C6-01
Application
Overload capability (oL2)
L3-02 Stall Prevention
during Acceleration
L3-06 Stall Prevention
during Run
Default carrier frequency
<1> Single-Phase AC200 V CIMR-JBA0001 to BA0006 : 10 kHz
Single-Phase AC200 V CIMR-JBA0010 : 8 kHz
Three-Phase AC200 V CIMR-J2A0001 to 2A0006 : 10 kHz
Three-Phase AC200 V CIMR-J2A0010 to 2A0020 : 8 kHz
Three-Phase AC400 V CIMR-J4A0001 to 4A0011 : 8 kHz
Reference and Run Source
The drive has a LOCAL and a REMOTE mode. The LED in the LO/RE key indicates the
drive status.
Status
LOCAL
The Run/ Stop command and the frequency reference are entered at the operator keypad.
The Run command source entered in parameter b1-02 and the frequency reference
REMOTE
source entered in parameter b1-01 are used.
If the drive is operated in the REMOTE mode, make sure that the correct sources for the
frequency reference and Run command are set in parameters b1-01/02 and that the drive is
in the REMOTE mode.
YASKAWA ELECTRIC TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
Heavy Duty Ratings (HD)
0
Applications with a constant torque like
extruders, conveyors and cranes. High
overload capability might be needed.
150% of drive rated current for 60 s
150%
150%
10 kHz, 8 kHz
Description
Applications where the torque increases with
the speed like fans or pumps. High overload
tolerance is normally not needed.
120% of drive rated current for 60 s
<1>
5 Start Up
Normal Duty Rating (ND)
1
120%
120%
Swing PMW
LO/RE LED
ON
OFF
EN 21