6 Parameter Table
Par.
Name
Stall Prevention
0:Disabled - Motor accelerates at
Stall
active acceleration rate and may
Prevention
stall with too heavy load or too
L3-01
Selection
short accel time.
during
1:General Purpose - Hold
Accel.
acceleration when current is
above L3-02.
Stall Prev.
Level
Sets the current level for stall
L3-02
during
prevention during acceleration.
Accel.
0:Disabled - Deceleration as set.
Stall Prev.
ov might occur.
Selection
1:General Purpose - Deceleration
L3-04
during
is hold if DC bus voltage rises
Decel.
high.
4:Overexcitation Deceleration
0:Disabled - Motor stall or
Stall Prev.
overload might occur.
L3-05
Selection
1:Decel Time 1 - Reduce speed
during Run
using C1-02.
2:Decel Time 2
Stall Prev.
Sets the current level at which stall
L3-06
Level
prevention during run starts to
during Run
operate.
Monitor
U1-01
Frequency Reference (Hz)
U1-02
Output Frequency (Hz)
U1-03
Output Current (A)
U1-06
Output Voltage Reference (Vac)
U1-07
DC Bus Voltage (Vdc)
Input Terminal Status
Reserved
U1-10
EN 26
Description
Description
: ON
: OFF
1: Digital input 1
(terminal S1 enabled)
1: Digital input 2
(terminal S2 enabled)
1: Digital input 3
(terminal S3 enabled)
1: Digital input 4
(terminal S4 enabled)
1: Digital input 5
(terminal S5 enabled)
YASKAWA ELECTRIC TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
Monitor
Output Terminal Status
U1-11
Reserved
U1-13
Terminal A1 input level
Fault Trace
U2-01
Current Fault
U2-02
Previous Fault
DI/DO
Sel.
Digital Input Function Selections
3
Multi-step speed reference 1
4
Multi-step speed reference 2
5
Multi-step speed reference 3
Jog frequency command (higher priority than
6
multi-step speed reference)
7
Accel/decel time selection
F
Not used (Set when a terminal is not used)
14
Fault reset (Reset when turned ON)
External fault; Input mode: N.O. contact /
20 to 2F
N.C. contact, Detection mode: Normal/during
operation
Digital Output Function Selections
During Run (ON: run command is ON or
0
voltage is being output)
1
Zero Speed
2
Speed Agree
6
Drive Ready
E
Fault
F
Not used
10
Minor fault (Alarm) (ON: Alarm displayed)
Description
: ON
: OFF
1: Relay Output
(terminal MA-MC closed
MB-MC open)
Description