Control Circuit Terminal Functions
Type
No.
Terminal Name (Signal)
S1
Multi-
to
Multi-function digital input 1 to 5
Function
S5
Digital
Inputs
SC
Multi-function input common
A1
Analog input
Analog
Input
+V
Analog input power supply
AC
Frequency reference common
Multi-
MA
N.O. (fault)
Function
MB
N.C. output (fault)
Relay
MC
Digital output common
Output
AM
Analog monitor output
Monitor
Output
AC
Monitor common
YASKAWA ELECTRIC TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
3 Electrical Installation
Function (Signal Level), Default Setting
Photocoupler inputs, 24 Vdc, 8 mA
Note: Drive preset to sinking mode (NPN). When using
source mode, set DIP switch S3 to "SOURCE" and use an
external 24 Vdc (±10%) power supply.
Sequence common
0 to +10 Vdc (20 k) resolution 1/1000
0/4 to 20 mA (250 ) resolution: 1/500
+10.5 V (max allowable current 20 mA)
0 V
Digital relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
0 to 10 Vdc (2 mA or less), Resolution: 1/256 (8 bit)
0 V