Electrical Ratings - Parker 650 Series Product Manual

Frame 1, 2 & 3
Hide thumbs Also See for 650 Series:
Table of Contents

Advertisement

Electrical Ratings

Note: For 3-phase units Frames 2 & 3, the Surge Current is less than the running current.
FRAME 1 : 1-Phase (IT/TN), 230V
Drive
Power
Surge Current
(kW/hp)
peak/rms for 10ms (A)
0.25/0.3
0.37/0.5
0.55/0.75
0.75/1.0
FRAME 2 : 1-Phase (IT/TN), 230V
Drive
Power
Surge Current
(kW/hp)
peak/rms for 10ms (A)
1.1/1.5
1.5/2.0
FRAME 2 : 3-Phase (IT/TN), 400V
Drive
Power
(kW/hp)
0.37/0.5
0.55/0.75
0.75/1.0
1.1/1.5
1.5/2.0
2.2/3.0
FRAME 3 : 1-Phase (IT/TN), 230V
Drive
Power
(kW/hp)
*
2.2/3.0
FRAME 3 : 3-Phase (IT/TN), 230V
Drive
Power
(kW/hp)
*
2.2/3.0
3.0/4
4.0/5
FRAME 3 : 3-Phase (IT/TN), 400V
Drive
Power
(kW/hp)
3.0/4
4.0/5
5.5/7.5
7.5/10
* The Frame 3, 2.2kW drive is capable of operating on a 1-phase or 3-phase supply.
Lefflersgatan 1, SE-754 50 Uppsala, SWEDEN
Motor power, output current and input current must not be exceeded under steady state
operating conditions.
Maximum Motor dv/dt = 10,000V/μs. This can be reduced by adding a motor choke in series
with the motor. Contact Eurotherm Drives for recommended choke details.
Local wiring regulations always take precedence. Select cable rated for the drive.
The supply must be protected with a fuse (or Type B RCD) rated to the supply cable.
Input Current @ 5kA
19/12
19/12
20/14
22/15
Input Current @ 5kA
24/17
25/18
Input Current @ 10kA
(A)
2.5
3.3
4.1
5.9
7.5
9.4
Input Current @ 7.5kA
(A)
22.0
Input Current @ 7.5kA
(A)
14.3
18.1
23.1
Input Current @ 10kA
(A)
11.1
13.9
18.0
23.6
+46 (0)18-65 70 00
Technical Specifications
Output Current @ 40
(A) ac
(A)
4.2
1.5
6.2
2.2
7.9
3.0
10.5
4.0
Output Current @ 40
(A) ac
(A)
13.8
5.5
16.0
7.0
Output Current @ 40
(A) ac
1.5
2.0
2.5
3.5
4.5
5.5
Output Current @ 40
(A) ac
9.6
Output Current @ 40
(A) ac
9.6
12.3
16.4
Output Current @ 40
(A) ac
6.8
9.0
12.0
16.0
+46 (0)18-10 74 78 info@regal.se www.regal.se
9-4
o
C
Maximum Power
Loss
(W)
26
32
41
52
o
C
Maximum Power
Loss
(W)
65
82
o
C
Maximum Power
Loss
(W)
26
32
40
55
61
70
o
C
Maximum Power
Loss
(W)
112
o
C
Maximum Power
Loss
(W)
103
133
180
o
C
Maximum Power
Loss
(W)
80
100
136
180
650 Series AC Drive

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents