5.3.1 Connections outside the housing

CAUTION!
T-coupling
Never connect a T-coupling directly to the housing.
The panel plug at the housing can break off.
CAUTION!
IP65 protection rating
Screw in the CAN cable threaded cable glands by
hand up to the stop. Otherwise the IP65 rating is not
achieved.
NOTICE!
Sequentially screw together the individual parts of the
CAN bus line starting from one side. Otherwise it can
occur that at one or several points socket is aligned
with socket or plug with plug.
CAN devices always have plugs, never sockets.
CAN bus line
External modules, CAN version of chlorine sensor and
DULCOMARIN
CAN bus line. The individual CAN devices are inserted
in this CAN bus line. There is a terminating resistance
at each end of the CAN bus line.
1.
Connect the supplied branching cables (e.g. 0.5 m) with a T-
piece on the end to each module and the DULCOMARIN
2.
Screw the T-pieces of the CAN modules sequentially
together using CAN cables or directly one after the other
3.
On each of the remaining ends of the CAN bus line screw on
a terminating resistance (1 x with a plug connector, 1 x with a
socket connector).
Assembly and installation
®
II are connected with each other via a
®
II
31