Installation (Electrical) - ProMinent DULCOMARIN II Assembly And Installation Manual

Multi-channel measuring and control system/swimming pool controller and disinfection controller dxca
Table of Contents

Advertisement

5.1.3 Installation (electrical)

8.
Remove the front part
9.
Now break out the necessary threaded holes of the lower
series, see
Ä Chapter 5.1.3 'Installation (electrical)'
on page 23
10.
Screw the back part to the control panel (using the supplied
PT screws)
11.
Plug the ribbon cable back on
12.
Move the front part into the
ð Now first electrically install the DULCOMARIN
then complete the control panel mounting.
13.
Place the front part on the rear part of the DXC housing and
screw it in
14.
CAUTION!
Protection class IP 54
Once again check the seating of the seal. Pro‐
tection class IP 54 is only achieved if the control
panel mounting is correct.
WARNING!
Failure of the circulating pumps
In the event that the circulating pump fails, it is not suf‐
ficient to use the sample water limit contact of the in-
line probe housing on its own in order to stop the con‐
trol for the corresponding pool (contact K1 of the M
module).
The pool controller must also be set to Pause using
the contact K2
Suitable triggers are:
the zero volt contact of the filter control
the zero volt contact of the circulation pump's
motor protection switch
a flow monitor in the circulation line
WARNING!
Safe operating status
Both hardware and software safety precautions must
be taken to ensure that the DULCOMARIN
safe operating status in the event of a fault. E.g. use
limit switches, mechanical locks, ...
During installation the device must not be electrically
live.
The installation must only be carried out by technically
trained personnel.
Observe the technical data in these instructions.
Assembly and installation
'park position'
'Pause control ' of the M module.
II and
®
®
II adopts a
23