Malfunctions - Samson 3725 Mounting And Operating Instructions

Electropneumatic positioner
Table of Contents

Advertisement

9 Malfunctions

In case of a fault, the fault indication icon
play the respective error code E0 to E15 together with ERR appear on the display. Refer to
the error code list in section 9.2 for the cause of the errors and the recommended action.
Example:
If, for instance, a travel has been entered in Code P4 (nominal range) which is larger than
the maximum valve travel possible, the initialization process would be interrupted (E2 error
code) because the rated travel would not have been reached (E6 error code). The valve
moves to the fail-safe position (S indicated on the display).
S
S
S
The nominal range (Code P4) must be changed and the positioner re-initialized to remedy
this problem.
EB 8394 EN
Display of the fault indication:
− Fault indication icon
− Valve moves to fail-safe position (S indicated on the display).
E2 error code: Initialization canceled.
E6 error code: Rated travel not achieved.
is displayed. Switch past Code P0 or P20 to dis-
appears.
Malfunctions
61