Operation

6 Operation

6.1 Operating controls

Three capacitive keys are used to operate the positioner and allow the user to navigate with-
in the menu on the display (Fig. 18). Additionally, the volume restriction allows the air output
capacity to be adapted to the size of the actuator.
6.1.1

Capacitive keys

: Up
: Confirm
: Down
Touch
or
key to select a parameter code (P0 to P20). Then touch
selected code.
To save changes to parameters in a non-volatile memory, proceed as follows:
Î After changing parameters, press
Î wait three minutes until the display returns automatically to P0.
Note
− The
icon on the display indicates that the changed parameter settings have not yet been
saved in the non-volatile memory.
− The selected parameter code remains active until you change the setting or exit the param-
eter code.
− After changing settings in P2, P4 and P8 parameter codes, the positioner must be re-initial-
ized.
6.1.2

Volume restriction Q

The volume restriction serves to adapt the air output capacity to the size of the actuator. Two
fixed settings are possible (refer to section 7.3).