Quick Start Guide
6.0

Post installation procedures

1. Perform hand measurement to the material.
2. Compare data with the result of distance measurement performed by the
Rosemount 5708:
a. Reference point for measurements and comparisons is the top part of the
antenna assembly.
b. Test the device while silo is idle.
c. Measure as close to the Rosemount 5708 as possible.
d. In some models, the device has minimum and maximum values for
distance. Check if the hand dip is between these measurement.
3. Coordinate filling and emptying processes.
a. Follow the Rosemount 5708 measurements during the process.
b. Check and compare distance.
c. Follow the log trends in Rosemount 3DVision.
4. Perform echo curve analysis and false echo mapping. For detailed
information, see the Rosemount 5708
5. Adjust advanced parameters. For more information, see the Rosemount
5708