Quick Start Guide
Map False Echoes
Reset Mapping
Distance To Map
False Echo
00.000 m
Decline Mapping
Approve Mapping
Decline Mapping
Approve Mapping
22
False Echo Area
3. Select Map False Echoes for
automatically mapping all the false
echoes up to a certain distance.
Or select Reset Mapping for deleting
the stored mapped false echoes from
the memory of the scanner.
Use the
key to go down the list.
Press
to continue.
E
a. If Map False Echoes is selected,
set the distance from the top of
the antenna assembly to the end
of the scanning point. Always
make sure to map false echoes
above material level. The
recommended level is 3 ft. (1 m)
above actual material level.
Use the
the two digits. Use the
modify the value. Press
continue.
b. Approve or decline the false echo
mapping operation.
Use the
list. Press
c. If Reset Mapping is selected,
approve or decline the operation.
Use the
list. Press
key to switch between
key to
to
E
key to go down the
to continue.
E
key to go down the
to continue.
E