4.2 Setting the polling address
Setting the device address is mandatory when multiple devices are connected
over an RS-485 Multidrop (daisy chain). Set the addresses prior to use of the
Rosemount 3DVision software.
<tag name>
3.45m Avg Dist.
█████████████▒▒▒▒▒
Basic Settings
Advanced Settings
False Echo Mapping
Polling Address
Polling Address
00
For the Rosemount 5708V and 5708S, only polling address configuration is
done using the LCD display.
The rest of the configuration is completed with the Rosemount 3DVision
software.
4.3
Configuring the Rosemount 5708L
Basic Settings configuration
<tag name>
3.45m Avg Dist.
█████████████▒▒▒▒▒
Basic Settings
Advanced Settings
False Echo Mapping
Polling Address
1. From the main screen, press the
to enter the main menu.
M
2. In the main menu, use the
to scroll down to Polling Address.
Press
Address configuration screen.
3. Use the
two digits. Use the
the value.
The default polling address is 00. The
polling address ranges from 00 to 63.
Press
and
1. From the main screen, press the
key to enter the main menu.
M
2. In the main menu, use the
keys to scroll down to Basic Settings.
Press
Settings screen.
to switch to the Polling
E
key to switch between the
key to modify
to store the modified address
E
to exit to the main screen.
ESC
to switch to the Basic
E
Quick Start Guide
key
E
/
keys
E
/
17