Emerson Rosemount 5708 Quick Start Manual page 20

3d solids
Hide thumbs Also See for Rosemount 5708:
Table of Contents

Advertisement

Quick Start Guide
Advanced Settings configuration
After configuring the Basic Settings, perform Advanced Settings configuration.
<tag name>
3.45m Avg Dist.
█████████████▒▒▒▒▒
Basic Settings
Advanced Settings
False Echo Mapping
Polling Address
Set Distance
To Full Calibration
00.500 m
Set Distance
To Empty Calibration
20.000 m
Set Adaptor Angle
00
20
Menu
1. From the main screen, press the
key to enter the main menu.
2. In the main menu, scroll down to
Advanced Settings, using the
Press
to switch to the Advanced
E
Settings configuration screen.
3. Set the distance from the mounting
plate (top of the scanner's antenna) to
the Full calibration point/100% level
point.
Use the
key to switch between the
two digits. Use the
the value. Press
4. Set the distance from the mounting
plate (top of the scanner's antenna) to
the Empty calibration point/0% level
point.
Use the
key to switch between the
two digits. Use the
the value. Press
5. Press
to keep the default setting.
E
Note: if using an angle adaptor, set the
angle value.
Use the
key to switch between the
two digits. Use the
the value. Press
July 2017
E
key.
key to modify
to continue.
E
key to modify
to continue.
E
key to modify
to continue.
E