Omron CP1H-X40D Operation Manual page 461

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Analog I/O Units
First Cycle ON Flag
A200.11
Always ON Flag
P_On
T0005
T0005
T0005
T0005
7-4-2
CP1W-MAD42/CP1W-MAD44 Analog I/O Units
MOV(021)
#8051
102
TIM
0005
#0002
Execution
condition
MOV(021)
2
D0
Execution
condition
MOV(021)
3
D1
Execution
condition
MOV(021)
D10
102
Execution
condition
CMP(020)
3
#8000
(P_EQ)
100.00
Each CP1W-MAD42 Analog I/O Unit provides 4 analog inputs and 2 analog
outputs.
Each CP1W-MAD44 Analog I/O Unit provides 4 analog inputs and 4 analog
outputs.
• The analog input range can be set to 0 to 5 VDC, 1 to 5 VDC, 0 to
10 VDC, −10 to 10 VDC, 0 to 20 mA, or 4 to 20 mA. The inputs have a
resolution of 1/12000.
An open-circuit detection function is activated in the ranges of 1 to 5 VDC
and 4 to 20 mA.
• The analog output range can be set to 1 to 5 VDC, 0 to 10 VDC, −10 to
10 VDC, 0 to 20 mA, or 4 to 20 mA. The outputs have a resolution of
1/12000.
← Writes the range code (8051) to the Unit.
← Reads analog input 0's converted value.
← Reads analog input 1's converted value.
← The content of D10 is written to the output
word as the analog output set value.
Open-circuit alarm
Section 7-4