Mounting
Space between Units When Expansion I/O Units Are Connected
1,2,3...
114
Unit
CP1H CPU Unit
Expansion I/O Unit, 32 or 40 I/O points
Expansion I/O Unit, 20 I/O points
Expansion I/O Unit, 16 outputs
Expansion I/O Unit, 8 inputs
Expansion I/O Unit, 8 outputs
Analog I/O Unit
Temperature Sensor Unit except CP1W-TS004 76 ±0.2
Temperature Sensor Unit CP1W-TS004
CompoBus/S I/O Link Unit
DeviceNet I/O Link Unit
CP1H CPU Unit
100 mm
1. Remove the cover from the CPU Unit's or the Expansion I/O Unit's expan-
sion connector. Use a flat-blade screwdriver to remove the cover from the
Expansion I/O Connector.
2. Insert the Expansion I/O Unit's connecting cable into the CPU Unit's or the
Expansion I/O Unit's expansion connector.
140 ±0.5
140 ±0.2
76 ±0.2
76 ±0.2
56 ±0.2
56 ±0.2
76 ±0.2
140 ±0.2
56 ±0.2
56 ±0.2
Expansion I/O Unit
Expansion I/O Unit
Expansion Unit
Expansion Unit
20 mm min.
10 mm min.
25 mm max.
15 mm max.
Section 3-3
A (mm)
Expansion
connector cover