Omron CP1H-X40D Operation Manual page 430

Cpu unit sysmac cp series
Hide thumbs Also See for CP1H-X40D:
Table of Contents

Advertisement

Analog Input Units
396
■ 0 to 20 mA Inputs
When the resolution is 1/6,000, the 0 to 20 mA range corresponds to hexa-
decimal values 0000 to 1770 (0 to 6,000). The range of data that can be con-
verted is FED4 to 189C hex (–300 to 6,300).
A negative current is expressed as two's complement.
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
−1 mA
0000 (0)
When the resolution is 1/12,000, the 0 to 20 mA range corresponds to hexa-
decimal values 0000 to 2EE0 (0 to 12,000). The entire data range is FDA8 to
3138 hex (–600 to 12,600).
A negative current is expressed as a two's complement.
Converted Data
Hexadecimal (Decimal)
3138 (12600)
2EE0 (12000)
−1 mA
0000 (0)
■ 4 to 20 mA Inputs
When the resolution is 1/6,000, the 4 to 20 mA range corresponds to hexa-
decimal values 0000 to 1770 (0 to 6,000). The range of data that can be con-
verted is FED4 to 189C hex (–300 to 6,300).
Current in the range of 3.2 to 4 mA is expressed as two's complement.
If an input is below the range (i.e., less than 3.2 mA), the open-circuit detec-
tion function is activated and the data becomes 8,000.
Converted data
Hexadecimal (Decimal)
189C (6300)
1770 (6000)
0000 (0)
FED4 (−300)
When the resolution is 1/12,000, the 4 to 20mA range corresponds to hexa-
decimal values 0000 to 2EE0 (0 to 12,000). The entire data range is FDA8 to
3138 hex (–600 to 12,600).
Current in the range of 3.2 to 4 mA is expressed as two's complement.
If an input is below the range (i.e., less than 3.2 mA), the open-circuit detec-
tion function is activated and the data becomes 8,000.
20 mA 21 mA
0 mA
FED4 (−300)
21 mA
0 mA
20 mA
FDA8 (−600)
3.2 mA
0 mA
20 mA 20.8 mA
4 mA
Section 7-2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cp1h-xa40dCp1h-y20dt-dCp1h

Table of Contents