High-speed Counters
Top
terminal
block
224
PLC Setup
Select the Use high speed counter 0 Option in the PLC Setup's Built-in Input
Tab.
Item
High-speed counter 0
Counting mode
Circular Max. Count
Reset method
Input Setting
I/O Wiring
Input Wiring
L1
L2/N COM
01
03
05
00
02
04
06
LG
Measurement
start switch
Output Wiring
P L1 PL2
Bottom
terminal block
+
00
01
COM C OM C OM COM
Range Comparison Table Settings
The inspection standards data is set in the DM Area with the CX-Programmer.
Even though range 1 is the only range being used, all 40 words must still be
dedicated to the range comparison table.
Word
Setting
D10000
#7430
D10001
#0000
D10002
#765C
D10003
#0000
D10004
#000A
Setting
Use high speed counter 0
Linear mode
---
Software reset
Up/Down inputs
07
09
11
01
03
05
07
08
10
00
02
04
06
CIO 100
PL1: OK indicator
PL2: NG indicator
02
03
0 4
0 6
00
01
05
07
C OM 02
CIO 1 00
Rightmost 4 digits of range 1 lower limit
Leftmost 4 digits of range 1 lower limit
Rightmost 4 digits of range 1 upper limit
Leftmost 4 digits of range 1 upper limit
Range 1 interrupt task number = 10 (A hex)
Section 5-2
09
11
08
10
CIO 101
03
04
06
05
07
COM
CIO 101
Function
Lower limit value:
30,000
Upper limit value:
30,300