Siemens SIPART PS2 Operating Instructions Manual page 129

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

6. Start the initialization process. To do this, press the
7. Determine the lower endstop of the actuator spindle.
8. Move the actuator to the desired position using the
9. Press the
10.Determine the upper endstop of the actuator spindle. Move the actuator to the desired
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
the display shows the following:
The current potentiometer position is output on the display after 5 seconds. Examples of
the displayed potentiometer positions are given below:
button. The current position of the actuator is applied. The display shows
the following:
Note
Fault message "RANGE"
The selected end position is beyond the permissible measuring range if the "RANGE"
message is output on the display. Correct the settings as follows:
1. Move the friction clutch until the display shows "OK".
2. Press the
button.
3. Move the actuator to another position using the
4. Abort the manual initialization process by pressing the
5. Then return to "P manual mode" mode.
6. Correct the actuator travel and the position detection.
position using the
or
button.
Commissioning
7.5 Commissioning linear actuators
button for at least 5 seconds until
or
button.
or
button.
button.
129